Portable Resistive 400 Hz Load Banks

A load bank is a device which develops an electrical load, applies the load to an electrical power source and converts or dissipates the resultant power output of the source.

The purpose of a load bank is to accurately mimic the operational or “real” load that a power source will see in actual application. However, unlike the “real” load, which is likely to be dispersed, unpredictable and random in value, a load bank provides a contained, organized and fully controllable load.
Consequently, a load bank can be further defined as a self-contained, unitized, systematic device that includes load elements with control and accessory devices required for operation.

Whereas the “real” load is served by the power source and uses the energy output of the source for some productive purpose, the load bank serves the power source, using its energy output to test, support or protect the power source.

Features

  • IC Load control device
  • Overheat and fan fail detection system
  • CB switching
  • Lightweight compact aluminum housing
  • Rugged design and durable construction
  • Powder Painting
  • All parts made of non-corrosive materials
  • Plug test pins for connecting external device measurement
  • Power indicator lights
  • + & – Indication
  • E&F circuit indicator
  • High Performance Cooling system
  • PWM Speed control function
  • Burnout protection at locked rotor
  • Measurements Overview
  • High quality analogue instruments 72 x 72 mm
  • Voltmeter 0-40 V, Ammeter 0-2500 A¸
  • 300 A continuous load with device which simulate an aircraft engine start
  • High quality Load and Rate switch
  • Standard aircraft 3-pole Power Receptacle with shield
  • Stainless steel feet on both the bottom and back panels
  • Power cable plug can be connected in either a horizontal or vertical position

Analogue Load Banks

Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 48 KW±5 %
Analogue Ammeter/Voltmeter Mov.iron – Class 1.5 A/V
Analogue Frequency Meter Mov.iron – Class 0.5 Hz
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 44.10
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 25 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 80 KW±5 %
Analogue Ammeter/Voltmeter Mov.iron – Class 1.5 A/V
Analogue Frequency Meter Mov.iron – Class 0.5 Hz
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 66.15
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 27 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 104 KW±5 %
Analogue Ammeter/Voltmeter Mov.iron – Class 1.5 A/V
Analogue Frequency Meter Mov.iron – Class 0.5 Hz
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 30 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 120 KW±5 %
Analogue Ammeter/Voltmeter Mov.iron – Class 1.5 A/V
Analogue Frequency Meter Mov.iron – Class 0.5 Hz
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 33 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 144 KW±5 %
Analogue Ammeter/Voltmeter Mov.iron – Class 1.5 A/V
Analogue Frequency Meter Mov.iron – Class 0.5 Hz
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 35 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality

Digital Load Banks (USB [D] or LAN/WiFi [DW] Connected)

Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 48 KW±5 %
3 line high brightness red led display class ±0.5% S acc. IEC 62053-22:2003 V / A / Hz / cosΦ / kW / kVA
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 44.10
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 26 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 80 KW±5 %
3 line high brightness red led display class ±0.5% S acc. IEC 62053-22:2003 V / A / Hz / cosΦ / kW / kVA
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 66.15
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 28 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 104 KW±5 %
3 line high brightness red led display class ±0.5% S acc. IEC 62053-22:2003 V / A / Hz / cosΦ / kW / kVA
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 31 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 120 KW±5 %
3 line high brightness red led display class ±0.5% S acc. IEC 62053-22:2003 V / A / Hz / cosΦ / kW / kVA
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 34 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality
Voltage 115 / 200 VAC ±10 %
Frequency  400 HZ ±10 %
Load/Power [KW/KVA] (cos=1) 144 KW±5 %
3 line high brightness red led display class ±0.5% S acc. IEC 62053-22:2003 V / A / Hz / cosΦ / kW / kVA
Load Test Proposal for GPU Testing Load raising within 30 sec from 0 to 100%
Hold on 100% for 5 min
Load decreasing within 10 min from 100 to 0%
Load Test Proposal for Engine Decarbonising Load raising within 30 sec from 0 to 100%
Hold on 100% for 45 min
Load decreasing within 15 min from 100 to 0%
Cooling-Forced [M³/MIN] 88.20
Standards ISO 6858, DSF 400, ARP 5015
Classification CE Marking, DIN, VDE, IEC
Operating Temperature -10 to +55ºC
Maximum Altitude 1000m (without downgrading), max 2000m
Relative Humidity 0% – 85% (W.O.Condensation)
Noise Level <70
Degree of Protection IP 21
Dimensions [LxWxH mm] 600x230x630 mm
Weight 36 kg
Painting Powder coating fine structure 71319 IGP / Swiss quality